11 Alarms 09.91
11.11 Alarm list ACKNOWLEDGE
6123
Illegal servo sampling time
Cause:
Effect:
Remedy:
NC MD 155 greater than 5
PLC STOP
Correct MD
6124
Gap in MC 5 memory
Cause:
Effect:
Remedy:
Legal and illegal blocks do not follow on smoothly
PLC STOP
Overall reset and reload PLC program
6125
Inputs assigned twice
Cause:
Effect:
Remedy:
Explanation:
Same address for central and distributed inputs
PLC STOP
Check addressing for input modules
Address central I/O device before distributed device
Cause:
Effect:
Remedy:
Explanation:
6126
Outputs assigned twice
Same address for central and distributed outputs
PLC STOP
Check addressing for output modules
Address central I/O device before distributed device
Cause:
Effect:
Remedy:
6127
Alarm byte missing
Selected interrupt input byte not available in hardware
PLC STOP
• Change PLC MD 0
• Adjust address decoding for interrupt byte
11–54 © Siemens AG 1990 All Rights Reserved 6ZB5 410-0DL02
SINUMERIK 810 GA3/820 GA3 (IA)