3 Installation and Commissioning
B−16
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
Step Explanation / meaning
6. Use the diagnostic functions during
commissioning and to analyze problems.
The following options are available:
S The LED displays on the CP
S Hardware diagnostics and troubleshooting with
STEP 7
S Communication diagnostics with STEP 7 / NCM
Diagnostics
S Standard information using HW Config
S Web diagnostics
S If applicable, evaluation of the alarm block
FB54 in the user program
S Queries via SNMP
7. Optional when using with PROFINET CBA:
Download PROFINET CBA component
If the S7 station in which the CP is operated is used
as a PROFINET CBA component, the
interconnections are downloaded using SIMATIC
iMap; for more detailed information, refer to the
topic “Using the CP with PROFINET CBA”.
Notice
Note the startup behavior:
Starting IT services, particularly when initializing the flash file system, may result in
delays during startup. It may be necessary to set the CPU parameter “Monitoring
time for transfer of parameters to modules” to a higher value − for example 30 s
instead of the default 10 s.
This avoids the CP changing to STOP “Stopped by error”.
You will find the parameter in the Properties dialog of the CPU in the “Startup” tab.