If you are using IRT communication, no media redundancy is supported.
9.8 Time-of-day synchronization
General rules
The CP supports the two modes explained below for time-of-day synchronization:
S SIMATIC mode
S NTP mode (NTP: Network Time Protocol)
Note
No automatic changeover to daylight saving is defined in NTP. As a result, you
may need to implement this changeover using a program application.
Notice
Note the following regarding time-of-day synchronization in NTP mode:
If the CP recognizes an NTP frame as being “not exact” (example: NTP server is
not externally synchronized), it is not forwarded to the communication bus. If this
problem occurs, none of the NTP servers is displayed as “NTP master” in the
diagnostics; rather all NTP servers are displayed only as being accessible.