5 Performance Data / Operation
B32
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
5.4 PROFINET IO
5.4.1 Characteristic data
Possible modes with PROFINET IO
With PROFINET IO, the CP can handle real-time communication (RT) and/or
isochronous real-time communication (IRT).
In this case, it can function as a PROFINET IO device and/or as a PROFINET IO
controller.
The following combinations of modes are possible:
S RT device + RT controller
S RT device + IRT controller
S IRT device + RT controller
The following combination is not possible:
S IRT device + IRT controller
Note
Note the information on IRT communication in Section 9.5.
CP as PROFINET IO controller
The CP supports the following maximum configuration as a PROFINET IO
controller:
Table 5-6
Characteristic
Explanation / values
Number of possible PROFINET IO devices 128, including a maximum of 32
IRT devices
If data is stored on the CPU, the
number of operable
PROFINET IO devices may be
< 128. This depends on the free
configuration memory available
on the CPU type you are using.
Size the input area over all PROFINET IO devices *) 4096 bytes max.
Size the output area over all PROFINET IO devices 4096 bytes max.