Siemens SIMATIC NET CP 343-1 Uživatelský manuál Strana 25

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 80
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 24
4 LED Displays
B25
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
LEDs for displaying the mode
The different combinations of the LEDs on the front panel indicate the status:
SF(red) BF1 / BF2
(red) *
)
RUN(gree
n)
STOP(yell
ow)
CP Operating Mode
S Starting up after power “ON”
or
S Stopped (STOP) with errors
For example no valid C-PLUG detected
In this state, the CPU or intelligent
modules in the rack remain accessible
using PG functions.
Starting up (STOP->RUN)
Running (RUN)
Stopping (RUN->STOP)
Stopped (STOP)
In the STOP mode configuring and performing
diagnostics on the CP remain possible.
S Interface networked but no LAN cable
inserted
or
S Duplicate IP address detected
The CP is configured as a PROFINET IO
device; there is no data exchange with the
PROFINET IO controller.
(BF2 only)
The CP (configured as a PROFINET IO
controller) has detected at least one IO device
as disrupted.
(BF2 only)
S RUN with external error; Diagnostic
message from one or more IO devices is
pending. IO device diagnostics will provide
detailed information.
or
S Event indication in conjunction with the
MRP function; The CP diagnostic buffer
contains detailed information.
Module fault / system error
Legend: (colored) on off (colored) flashing ” any
*) The behavior applies to BF1 and BF2 if there is no restriction listed in the “CP mode” column.
Zobrazit stránku 24