CP 523 Communications Mode
Example: Transferring parameter setting data for parameter block 0
Start address 128 is set on the CP 523.
You can set its parameters as follows:
Parameters for the serial interface (parameter block 0)
2400 baud (06
H
)
Even parity (00
H
)
No BUSYsignal (00
H
)
RS-232-C (V.24) interface (01
H
)
7 data bits (11-bit character frame) (00
H
)
Handshaking OFF (00
H
)
* 5.2
** The program waits at FB 99 until the CP 523 can accept job request ( 4.1)
STL FB 110STL OB 22 Explanation
:JU FB 99
NAME :SYNC**
:JU FB 110
NAME :BLOCK0
:BE
Handshaking OFF
7 data bits (11-bit character frame)
No BUSY signal
RS-232-C (V.24) interface
2400 baud
Even parity
Transfer "Parameter setting data
parameter block 0" job number
NAME :BLOCK0
:L KH 0000
:T PW 134
:L KH 0001
:T PW 132
:L KH 0600
:T PW 130
:L KH 9000
:T PW 128 *
:BE
Restart organization block OB 22 is only processed if the CPU is in RUN mode before you switch
from "POWER OFF" to "POWER ON".
Note:
The status byte can be scanned approx. 30 ms after the request was issued in order to check
whether correct parameter setting data was transferred (X4 is returned to indicate errored
values ( 7.4.1)).
Note:
EWA 4NEB 811 6044-02a
7-29