CP 523 Print Mode
6.3.5 Configuring the Correction Value for the Integral Clock
(Parameter Block 9)
You can configure a correction value to increase the accuracy of the clock. The correction value is
printed in s/month. A month is defined as 30 days.
Table 6-6. Correction Value for the Integral Clock (Parameter Block 9)
Default ValueValue RangeParameter
Correction value -400
D
to +400
D
s/month 0000
D
Note:
The correction value must always be specified as a four-digit number (incl. sign)!
Example: Determining the correction value
You have observed that the clock loses 12 s in 4 days. This would amount to 90 s in 30 days. The
correction value is then +090 s/month.
ExplanationEntry on the PG for DB 1
Block separator ”:”
Parameter block number ”9”
Correction value "+090"
: KS = ':9+090';
EWA 4NEB 811 6044-02a
6-13