Hardware Installation CP 523
3.4 Terminal Diagrams
This section contains typical terminal diagrams for connecting the following:
A printer (PT 88)
A point-to-point connection (data terminal equipment DTE)
- CP 523 to CP 523
- CP 523 to CPU 944
Modem link (data communications equipment DCE)
3.4.1 Terminal Diagrams for Print Mode
The CP 523 assumes a printer with an RS-232-C (V.24) or TTY interface as the peripheral device.
CP 523 (passive TTY) to PT 88 (active TTY) without BUSY signal
Figure 3-6. Pin Assignments for CP 523 (Passive TTY) to PT 88 (Active TTY) without BUSY Signal
PT 88
Shield (24) (1) Shield
Shield (25)
TTY OUT - (12) (9) TTY IN+
TTY OUT+ (10) (10) TTY IN –
20 mA
CP 523
CP 523 (passive TTY) to PT 88 (active TTY) with BUSY signal
Figure 3-7. Pin Assignments for CP 523 (Passive TTY) to PT 88 (Active TTY) with BUSY Signal
TTY IN+ (6) (21) TTY OUT -
Shield (24) (1) Shield
Shield (25)
TTY OUT+ (10) (10) TTY IN -
TTY OUT - (12) (9) TTY IN+
TTY IN - (8) (18) TTY OUT+
20 mA
CP 523 PT 88
20 mA
Printer setting: Printer not ready to receive = no current
3-8
EWA 4NEB 811 6044-02a