Print Mode CP 523
6.3.3 Configuration Data for Message Text Printout (Parameter Blocks 4 to 6)
If you enter an illegal value, the CP will replace it with the relevant default value.
If the lower limit is exceeded, the lower limit value is set.
If the upper limit is exceeded, the upper limit value is set.
Example:
Input: Lines per page "10
H
" is replaced by "14
H
"
Input: Left margin "80
H
" is replaced by "3C
H
"
Table 6-4. Configuration Data for Message Text Printout (Parameter Blocks 4 to 6)
Description Default Value
on the CP 523
Parameter
Block
Any combination of year,
month and day is
permissible
(lowercase also permissible)
ASCII character (20
H
to 7F
H
)
HMS, HSM, MSH, MHS, SHM,
SMH
(lowercase also permissible)
ASCII character (20
H
to 7F
H
)
d, D
e, E
TMJ
”.” (2E
H
)
HMS
”:” (3A
H
)
D (24h clock)
4
Page format
Lines per page
Left margin
Page number
top
bottom
none
14
H
to FF
H
00
H
to 3C
H
o, O, h, H
u, U, f, F
other characters
48
H
(72
D
)
00
H
u
5
Header and footer
Header 1
Header 2
Footer 1
Footer 2
K1”Text”, H1”Text”
K2”Text”, H2”Text”
F1”Text”
F2”Text”
No header or
footer
6
Date and time of day:
Order for date
J,Y = Year
M = Month
T,D = Day
Separator for date
Order for time of day
H = Hours
M = Minutes
S = Seconds
Separator for time of day
24h clock
12h clock
Value Range
6-8
EWA 4NEB 811 6044-02a