Communications Mode CP 523
Setting parameters for the 3964(R) MODE in the USER PROGRAM
Transferring the parameter setting data for parameter block 0
Table 7-18. Transfer Memory Assignments for ”Transfer Parameter Setting Data
for Parameter Block 0”
Default Values
on the CP 523
Possible ValuesDescriptionByte
0 Job number
”Transfer parameter setting”
90
H
1 Bits 4 to 7: Parameter block number
Bits 0 to 3: Relevant for parameter
blocks 7 and 9 only
00
H
2
3
Baud rate 110 baud
200 baud
300 baud
600 baud
1200 baud
2400 baud
4800 baud
9600 baud
01
H
02
H
03
H
04
H
05
H
06
H
07
H
08
H
Parity even
odd
”mark”
”space”
no parity check
00
H
01
H
02
H
03
H
04
H
-
-
04
H
00
H
4 BUSY signal No 00
H
00
H
5 Interface TTY
V.24
00
H
01
H
00
H
6
7 HW handshake OFF
ON
00
H
01
H
00
H
00
H
00
H
01
H
02
H
03
H
04
H
05
H
Data format: Parity:
11-bit character 7 data bits (yes)
frame 8 data bits (yes)
8 data bits (no)
10-bit character 7 data bits (no)
frame 7 data bits (yes)
8 data bits (no)
7-38
EWA 4NEB 811 6044-02a
Komentáře k této Příručce