Overview of alarms 06/2009
NCK alarms
2-20
© Siemens AG 2009 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2009
MD10240: $MN_SCALING_SYSTEM_IS_METRIC
MD10250: $MN_SCALING_VALUE_INCH
MD30300: $MA_IS_ROT_AX
If these data are modified, the NCK must be powered up again. Only then will the input of dependent
data be performed correctly.
Reaction: Alarm display.
Remedy: Please inform the authorized personnel/service department.
If the alarm has been displayed after downloading an MD file which is consistent within itself, then the
download operation must be repeated with a new NC power-up. (The file contains scaling-dependent
machine data in front of the scaling factors).
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
4071 Check the position of the encoder
Definitions: A machine data has been changed that affects the value of an encoder position. Please check the
position values.
For absolute value encoders:
Encoder adjustment has been changed, the machine reference of the axis position may have
changed, check the encoder adjustment.
Other encoders:
The reference point of the axis position has been changed, check the referencing procedure.
Reaction: Alarm display.
Remedy: Please inform the authorized personnel/service department.
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
4075 Machine data %1 (and maybe others) not changed due to missing
permission level %2
Parameters: %1 = String: MD identifier
%2 = Write protection level of the MD
Definitions: On executing a TOA file or when writing machine data from the part program, an attempt has been
made to write an item of data with a higher protection level than the access authorization currently set
in the control. The item of data in question has not been written and program execution is continued.
This alarm is set only when access violation is detected for the first time.
Reaction: Alarm display.
Remedy: Please inform the authorized personnel/service department. Set the required access level by means
of keyswitch or password entry or delete the machine data concerned from the MD file/part program.
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
4076 %1 Machine data could not be changed with permission level %2
Parameters: %1 = Number of MDs
%2 = Preset access authorization
Definitions: On executing a TOA file or when writing data from the part program an attempt has been made to write
data with a higher protection level than the access authorization currently set in the control. The data
in question have not been written and program execution is continued without hindrance. This alarm
is issued on acknowledging alarm 4075. It can be cleared only with Power ON.
Reaction: NC Start disable in this channel.
Alarm display.
Remedy: Please inform the authorized personnel/service department. Set the required access level by means
of keyswitch or password entry or delete the machine data concerned from the MD file/part program.
Program Con-
tinuation:
Switch control OFF - ON.
4077 New value %1 of MD %2 not set. Requested %3 bytes too much %4
memory.
Parameters: %1 = New value of machine data
%2 = Machine data number
%3 = Number of bytes requested that exceeded availability
%4 = Type of memory