NCK alarms
06/2009 Overview of alarms
2-47
© Siemens AG 2009 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2009
Definitions: Gantry error limit exceeded status (alarm 10653) has been switched off.
The error can only be removed by deleting MD37135 $MA_GANTRY_ACT_POS_TOL_ERROR or by
deactivating the extended monitoring (MD37150 $MA_GANTRY_FUNCTION_MASK Bit0).
Reaction: NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Please inform the authorized personnel/service department.
1. Remove a mechanical misalignment
2. Check axis (uneven mechanical movement?)
3. Delete MD37135 $MA_GANTRY_ACT_POS_TOL_ERROR or deactivate the extended monitoring
4. MD37120 $MA_GANTRY_POS_TOL_ERROR is set incorrectly
If the MD is changed, a Power ON will be required.
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
10658 [Channel %1: ] Axis %2 impermissible axis status %3.
Parameters: %1 = Channel number
%2 = Axis number
%3 = Error ID and gantry unit.
Definitions: Error ID and gantry unit
- 30XX => Gantry group cannot be closed, as not all gantry axes are in one channel.
- 40XX => Gantry group cannot be closed, as the gantry axes have different axis states, for example
the axis is assigned to the PLC.
- 50XX => Gantry group is to change channel due to a PLC request, not all gantry axes are known in
the new channel.
- 60XX => Gantry group is to be transferred to the channel due to an NC program request, but the
channel does not know all the gantry axes.
Reaction: NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Error ID:
- 30XX => assign all gantry axes to the current channel, for example via axis exchange.
- 40XX => set all axes of the gantry group to the same axis state, for example assign all axes to the
NC program, or assign all axes to the PLC.
- 50XX => make all gantry axes known to the required channel.
- 60XX => make all gantry axes known to the required channel.
:end
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
10720 [Channel %1: ] Block %3 axis %2 software limit switch %4
Parameters: %1 = Channel number
%2 = Axis name, spindle number
%3 = Block number, label
%4 = String (+ or -)
Definitions: The path programmed for the axis violates the currently valid software limit switch. The alarm is acti-
vated when preparing the part program block.
If bit 11=0 in the machine data MD11411 $MN_ENABLE_ALARM_MASK, this alarm is issued instead
of alarm 10722. If bit 11 is set in the machine data MD11411 $MN_ENABLE_ALARM_MASK, an
expanded diagnostics option is offered for the software limit switch violation. The condition for activa-
tion is the presence of the ALUN* alarm file in the HMI.
Reaction: Correction block is reorganized.
Local alarm reaction.
Interface signals are set.
Alarm display.
Remedy: Check and correct positions in the NC program.
Please inform the authorized personnel/service department.
Check machine data: MD36100 $MA_POS_LIMIT_MINUS / MD36120 $MA_POS_LIMIT_MINUS2
and MD36110 $MA_POS_LIMIT_PLUS / MD36130 $MA_POS_LIMIT_PLUS2 for the software limit
switches.