Overview of alarms 06/2007
NCK alarms/ISO alarms
2-184
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007Edition
16904 Channel %1 program control: action %2<ALNX> not allowed in the
current state
Parameters: %1 = channel number
%2 = action number/action name (see Section 1.5 Action List)
Definitions: The operation (program, JOG, block search, reference point, etc.) cannot be started or continued in
the current status.
Reaction: Alarm display.
Remedy: Check the program status and channel status.
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
16905 Channel %1 program control: action %2<ALNX> not allowed
Parameters: %1 = channel number
%2 = action number/action name (see Section 1.5 Action List)
Definitions: Operation cannot be started or continued. A start is only accepted when an NC function can be
started.
Example: A start is accepted in JOG mode when, for example, the function generator is active or a
JOG movement has first been stopped with the Stop key.
Reaction: Alarm reaction in Automatic mode.
Remedy: Check the program and channel status.
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
16906 Channel %1 program control: action %2<ALNX> is aborted due to an
alarm
Parameters: %1 = channel number
%2 = action number/action name (see Section 1.5 Action List)
Definitions: The action was aborted due to an alarm.
Operation cannot be started or continued. A start is only accepted when an NC function can be
started.
Reaction: Alarm display.
Remedy: Eliminate the error and acknowledge the alarm. Then repeat the operation.
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
16907 Channel %1 action %2<ALNX> only possible in stop state
Parameters: %1 = channel number
%2 = action number/action name (see Section 1.5 Action List)
Definitions: This action may only be performed in Stop state.
Reaction: Alarm display.
Remedy: Check the program and channel status.
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
16908 Channel %1 action %2<ALNX> only possible in reset state or at the block
end
Parameters: %1 = channel number
%2 = action number/action name (see Section 1.5 Action List)
Definitions: The action %2 may only be performed in Reset state or at end of block.
Reaction: Alarm display.
Remedy: Check the program and channel status.
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.