NCK alarms/ISO alarms
06/2007 Overview of alarms
2-195
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007Edition
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
16952 Channel %1 start program command not possible due to MDI
Parameters: %1 = channel ID
Definitions: The NCK is currently processing an ASUB in MDA mode. In this state, it is not legal to issue a "Start"
program command for another channel. Notice! If an asynchronous subprogram is started from JOG,
the NCK can switch internally to MDA if it was previously in this mode and has not been RESET. Note:
With-out this alarm, the MDA buffer of the other channel would always be started.
Reaction: NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Start asynchronous subroutine in AUTO or AUTO->JOG
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
16953 Channel %1 For slave axis %2 SERUPRO not allowed, as master axis %3
not subject to axis/spindle disable
Parameters: %1 = Channel number
%2 = Slave axis name, following spindle number
%3 = Master axis name, master spindle number
Definitions: Currently, the alarm occurs only in combination with the SERUPRO action. SERUPRO stands for
search via program test.
SERUPRO is possible only with an active coupling, if the axis/spindle disable is active for all master
axes/spindles of the slave axis/spindle
Reaction: NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Set axis/spindle disable of the master axis
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
16954 Channel %1 block %2 programmed stop prohibited in stop delay area
Parameters: %1 = channel ID
%2 = block number, label
Definitions: A program command which causes a stop has been used in a program area (stop-delay area) which
is parenthesized by DELAYFSTON and DELAYFSTOF. Except for G4, no commands which cause
even a brief stop may be used in such areas. A stop-delay area can also be defined via MD 11550
STOP_MODE_MASK.
Reaction: Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: MD 11550 STOP_MODE_MASK and NC command DELAYFSTON DELAYFSTOF
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
16955 Channel %1 stop in stop delay area is delayed
Parameters: %1 = channel ID
Definitions: An event which causes a stop has been detected in a program area (stop-delay area) which is paren-
thesized by DELAYFSTON and DELAYFSTOF. The stop is delayed and executed after DELAYF-
STOF. A stop-delay area can also be defined via MD 11550 STOP_MODE_MASK.
Reaction: Interface signals are set.
Alarm display.
Remedy: MD 11550 STOP_MODE_MASK and NC command DELAYFSTON DELAYFSTOF
Program Con-
tinuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.