Overview of alarms 06/2007
NCK alarms/ISO alarms
2-200
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007Edition
Remedy: Remove write access operations to protected variable from the NC program or machine data file.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
17080 Channel %1 block %2 %3 value below lower limit
Parameters: %1 = channel number
%2 = block number, label
Definitions: An attempt was made to write an MD with a value that is smaller than the defined lower limit.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Please inform the authorized personnel/service department.
Determine the input limits of the MD and assign a value within these limits.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
17090 Channel %1 block %2 %3 value exceeds upper limit
Parameters: %1 = channel number
%2 = block number, label
Definitions: An attempt was made to write an MD with a value that is higher than the defined upper limit.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Please inform the authorized personnel/service department.
Determine the input limits of the MD and assign a value within these limits.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
17095 Channel %1 block %2 invalid value
Parameters: %1 = channel number
%2 = block number, label
Definitions: An attempt was made to write an invalid value, e.g. zero, into a machine data.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Correct the value assignment, e.g. a value within the value range not equal to zero.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
17100 Channel %1 block %2 digital input/comparator no. %3 not activated
Parameters: %1 = channel number
%2 = block number, label
%3 = no. of input
Definitions: Either an attempt was made to read a digital input n via the system variable $A_IN[n] and this input
has not been activated via NCK machine data 10350 FASTIO_DIG_NUM_INPUTS; or to read a com-
parator input via system variable $A_INCO[n] and this input belongs to a comparator which has not
been activated.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Please inform the authorized personnel/service department. Modify part program or machine data
accordingly.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
17110 Channel %1 block %2 digital output no. %3 not activated
Parameters: %1 = channel number
%2 = block number, label
%3 = no. of output